CHS_LHS

31242827EN-03 29 LU-VE Exchangers is a trademark registered and owned by LU-VE Group. LU-VE Exchangers reserves the right to change specifications without prior notification. 6.3 Electric defrost elements replacement Before handling heater elements always: • disconnect power supply • ensure heaters are at ambient temperature. Electric defrost elements in coil To remove electric defrost elements in coil (RCL and FCL) • open the side covers on both sides • disconnect heater element from connection box • disconnect heater protection, if any • remove fixing clip (U) and extract element from coil • mount new element in reverse order and reassamble the fixing clip in the correct position (V) • restore electrical connections and close side covers. FCL RCL NO-NO-NON-NEIN-NO ≥ 1300 mm ≥ 1300 mm Ø 8.5 mm Ø 9.35 mm Tubo-Tubes-Tubes-Rohr-Tube U SI-YES-OUI JA-SI Ø 9 mm RCL U V FCL heater protection Electric defrost elements in drain tray To remove heater elements (FCL) in drain tray: • open the drain tray • disconnect heater element • remove element from bottom • mount new element in reverse order • close drain tray and restore electrical connections.

RkJQdWJsaXNoZXIy Mzc3NTY=