CHS_LHS

31242827EN-03 17 LU-VE Exchangers is a trademark registered and owned by LU-VE Group. LU-VE Exchangers reserves the right to change specifications without prior notification. 5.10 Fan motor connections, EC fans Model Diameter (mm) Type Nominal Voltage range (V) Phase Freq. (Hz) Power Cons. (W) Current draw (A) CS/LS/ECS 45 450 EC 200-277 1ph 50-60 410 1.8 Model Diameter (mm) Type Nominal Voltage range (V) Phase Freq. (Hz) Power Cons. (W) Current draw (A) CS/LS/ECS 50 500 EC 380-480 3ph 50-60 1000 1.6 CS/LS/ECS 62 630 EC 380-480 3ph 50-60 1080 1.7 PE PE L NC COM GND RSB 0-10V RSA 0-10V N fan Ø 450 mm fan Ø 500, 630 mm fan Ø 710, 800, 910, 950 mm Model Diameter (mm) Type Nominal Voltage range (V) Phase Freq. (Hz) Power Cons. (W) Current draw (A) CS/LS/ECS 71 710 EC 380-480 3ph 50-60 3700 5.6 CS/LS/ECS 80 800 EC 380-480 3ph 50-60 2200 3.4 CS/LS 90 910 EC 380-480 3ph 50-60 2600 4.0 CS/LS 95 950 EC 380-480 3ph 50-60 2550 3.9 Minimum working temperature of EC standard fans: -25 °C. Contact LU-VE Exchangers, for special version that can reach lower temperature.